123
Remote Adapters Section 4-6
Refer to the wiring details for each Slave for information on the terminal
arrangement at the terminal block. The following example shows the internal
power supply for a DRT1-ID16X Remote Input Adapter.
Wiring the I/O Power
Supply
The I/O power supply and I/O are wired through the MIL socket on the I/O flat
cable connector. An MIL connector for an I/O Relay Block or PCB can be con-
nected.
Connecting to I/O Relay Blocks
The MIL socket on the flat cable connector on the Remote Adapter can be
connected directly to the connector on an OMRON I/O Relay Block.The
Remote Adapter-I/O Relay Block combinations that can be connected are
listed in the following table.
Note 1. Connection is also possible to manifold solenoid valves from Koganei or
CKD.
2. The DRT1-ID16X-1 cannot be connected to an I/O Relay Block.
Connecting to PCB MIL Connectors
The MIL socket on the flat cable connector on the Remote Adapter can be
connected to I/O devices connected to a PCB by connecting a MIL connector
to the PCB. The PCB MIL connectors that can be used are listed in the follow-
ing table.
REMOTE ADAPTER 24VDC
No.
NSMS
DRT1-ID16X
+
Remote Adapter I/O Relay Block
DRT1-ID16X G7TC-ID16-5
G7TC-IA16-5
DRT1-OD16X G7TC-OC08
G7TC-OC16
G70D-SOC16
G70D-FOM16
G70A-ZOC16-3
MIL Connector Remarks
XG4A-2031 DIP straight terminals
XG4A-2034 DIP right-angle terminals