Analog I/O Terminals Section 4-8
DRT1-AD04
–10- to 10-V Inputs
The –10- to 10-V range corresponds to the hexadecimal values 8BB8 to 0BB8
(–3000 to 3000). The most significant bit (bit 15) is set to 1 (ON) for negative
values and the AD conversion data is set to the absolute values; the rest of
the word indicates the absolute value. The entire data range is 8CE4 to 0CE4
(–3300 to 3300).
0- to 10-V Inputs
The 0- to 10-V range corresponds to the hexadecimal values 0000 to 1770 (0
to 6000). The most significant bit (bit 15) is set to 1 (ON) for negative values
and the AD conversion data is set to the absolute values; the rest of the word
indicates the absolute value. The entire data range is 812C to 189C (–300 to
6300).
0- to 5-V Inputs
The 0- to 5-V range corresponds to the hexadecimal values 0000 to 1770 (0
to 6000). The most significant bit (bit 15) is set to 1 (ON) for negative values
and the AD conversion data is set to the absolute values; the rest of the word
indicates the absolute value. The entire data range is 812C to 189C (–300 to
6300).
0CE4 (3300)
0BB8 (3000)
–11 V –10 V
0 V 10 V 11 V
8BB8 (–3000)
8CE4 (–3300)
0000 (0)
Converted data
Hexadecimal (decimal)
Voltage
189C (6300)
1770 (6000)
– 0.5 V
0 V812C (–300) 10 V 10.5 V
0000 (0)
Converted data
Hexadecimal (decimal)
Voltage
189C (6300)
1770 (6000)
– 0.25 V
0 V 5 V 5.25 V
812C (–300)
0000 (0)
Converted data
Hexadecimal (decimal)
Voltage