Analog I/O Terminals Section 4-8
Components
Ambient operating
environment
No corrosive gases.
Ambient storage tem-
perature
25 to 65°C
Mounting method M4 screw mounting or 35-mm DIN track mounting
Mounting strength 50 N
10 N min. in the DIN Track direction
Terminal strength Pull: 50 N
Weight 160 g max.
Output signal range 1 to 5 V, 0 to 10 V, or –10 to
10 V
0 to 20 mA or 4 to 20 mA
Allowable external out-
put load resistance
1 K min. 600 max.
Output impedance 0.5 max. ---
Resolution 1/6000 (full scale)
Accuracy 25°C ±0.4% FS
0 to 55°C ±0.8% FS
Conversion time 4 ms/2 points
Conversion output
data
(Binary)
–10- to 10-V range: 8BB8 to 0 to 0BB8 full scale
Other signal ranges: 0000 to 1770 full scale
Isolation method Photocoupler isolation between analog outputs and commu-
nications lines
(There is no isolation between analog output signals.)
Item Specification
Voltage outputs Current outputs
DIN track mounting hooks
DeviceNet Indicators
Communications connector
DIP switch
Pins 1 to 6: Node address setting
Pins 7 and 8: Baud rate setting
Pins 9 and 10: O tp t stat s after comm nications error
Rotary switch
Sets the output ranges.
Terminal block
Connect the internal circuits power
supply and the analog outputs.
(Refer to page 312.)
(Refer to page 40.)
Pins 1 to 6: Node address setting
Pins 7 and 8: Baud rate setting
Pins 9 and 10: Output status after communications error