163
Temperature Input Terminals Section 4-9
The four inputs occupy four words at the Master, as shown below. If the input
classification is set for up to one digit below the decimal point, a multiple of 10
will be transmitted as binary data.
Note 1. For more details regarding temperature conversion data with a unit setting
of two digits below the decimal point (unit: 0.01), refer to page 164.
2. If there is a sudden temperature change, condensation may develop inside
of the Terminal and cause incorrect values to be displayed. If condensation
does develop, leave the Terminal for approximately one hour at a stable
temperature before using it.
Data Ranges and the
Open-circuit Detection
Function
The following table shows the convertible data ranges according to the num-
ber set by the rotary switch.
DRT1-TS04T
Bit
Beginning word
Beginning word + 1
Beginning word + 2
Beginning word + 3
Input 0: Temperature conversion data
Input 1: Temperature conversion data
Input 2: Temperature conversion data
Input 3: Temperature conversion data
Input classifi-
cation
Unit: 1°C (°F) R, S, K1, J1, E,
L1, N, W, B, PL
850° 0352 (4 digits hex)
–200° FF38 (4 digits hex)
Unit: 0.1°C (°F) K2, J2, T, L2, U,
Pt100, JPt100
x10
500.0° 5000 1388 (4 digits hex)
–20.0° 200 FF38 (4 digits hex)
–200.0° 2000 F830 (4 digits hex)
Number Input classification Range (°C) Range (°F)
0 R –20 to 1720 –20 to 3020
1 S –20 to 1720 –20 to 3020
2 K1 220 to 1200 –320 to 2320
3 K2 –20.0 to 520.0 –20.0 to 920.0
4 J1 –120 to 870 120 to 1520
5 J2 –20.0 to 420.0 –20.0 to 770.0
6 T –220.0 to 420.0 –320.0 to 720.0
7 E –20 to 620 –20 to 1120
8 L1 –120 to 870 120 to 1520
9 L2 –20.0 to 420.0 –20.0 to 770.0
A U –220.0 to 420.0 –320.0 to 720.0
B N –220 to 1320 –320 to 2320
C W –20 to 2320 –20 to 4120
D B 80 to 1820 280 to 3220
E PL II –20 to 1320 –20 to 2320
F Cannot be set.