221
B7AC Interface Units Section 5-5
2. This bit is always 0 (OFF).
I/O Allocation Example
When the Master Unit is mounted in a C200HX/HG/HE PLC and fixed alloca-
tion is used for DeviceNet, IR area words IR 350 through IR 399 are allocated
to inputs from Slaves with node addresses 0 through 49.
If the B7AC Interface Unit’s node address is set to 01, the first allocated word
(m+0) will be IR 351. Ports A, B, and C will be allocated the following bits:
IR 35214 is the B7AC Communications Error Flag for the B7AC Interface
Unit.
Note If a communications error occurs in communications with a B7AC Link Termi-
nal Unit, normal communications will be restored automatically when the com-
munications error is resolved. The time required to restore communications
depends on the error continuation time (time from error occurrence to error
resolution), as shown below.
Error continuation time less than 500 ms:
The B7AC Communications Error Flag will be turned OFF 500 ms after
the error occurred.
Error continuation time greater than 500 ms:
The B7AC Communications Error Flag will be turned OFF after the er-
ror is resolved.
Port on B7AC
Interface Unit
Connector on B7AC Link
Terminal Unit
I/O bits allocated to Master Unit
Port A Input connector 0 to 9 IR 35100 to IR 35109
Port B Input connector 0 to 5 IR 35110 to IR 35115
Input connector 6 to 9 IR 35200 to IR 35203
Port C Input connector 0 to 9 IR 35204 to IR 35213
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0
m+0: Wd 351
m+1: Wd 352
ERR
B7AC Communications Error Flag B7AC Unit connected to port A
B7AC Unit connected to port B
B7AC Unit connected to port C