290
RS-232C Units Section 6-2
Port 1 and 2 resetting common data
Response storage words: DM 0450
(82 Hex: DM; 01C2 Hex: word 450; 00 Hex: Word data
)
Response monitoring time: 10 s
Number of command data bytes: 8 bytes
EXPLICIT MESSAGE SEND command code (FINS):
2801 Hex
Slave node address: 08
RS-232C PORT RESET command service code:
05 Hex
Class ID: 94 Hex
MOV(21)
#8201
DM0400
25315
MOV(21)
#C200
DM0401
MOV(21)
#0064
DM0402
MOV(21)
#0008
DM0403
MOV(21)
#2801
DM0404
MOV(21)
#0805
DM0405
MOV(21)
#0094
DM0406
Port 1 parameter setting data
Port 2 parameter setting data
ALL PARAMETER SET Attribute ID: 64 Hex
8-bit data length, no parity, 1 stop bit: 08 Hex
Disabled header code, enabled delimiter code,
enabled flow control: 01 Hex
9,600-bps baud rate: 03 Hex
Delimiter code: CR code (0D Hex)
Number of transmission bytes after delimiter: 0
ALL PARAMETER SET Attribute ID: 6B Hex
7-bit data length, even parity, 2 stop bits: 03 Hex
Enabled header code, enabled delimiter code, dis-
abled flow control: 04 Hex
2,400-bps baud rate: 01 Hex
Delimiter code: ETX code (03 Hex)
Number of transmission bytes after delimiter: 0
Header code: STX code (02 Hex)
25315
MOV(21)
#6408
DM0020
MOV(21)
#0103
DM0021
MOV(21)
#000D
DM0022
MOV(21)
#0000
DM0023
MOV(21)
#6B03
DM0024
MOV(21)
#0203
DM0026
MOV(21)
#0000
DM0027
MOV((21)
#0401
DM0025