25
Checking Operations Section 2-5
I/O between Remote I/O
Terminals
Create ladder programs in the PLC of the Master Unit, and check that when
the switch on the DRT1-ID16 Input Terminal turns ON, the indicator on the
DRT1-OD16 Output Terminal turns ON.
Slave Allocations
In the system configuration examples in this section, Slave I/O is allocated in
the Master Unit’s IR Area for fixed remote I/O communications as shown in
the following diagram.
Displaying Temperature
Data with 7-segment
Display
Operation can be checked by displaying the temperature data input into the
Temperature Input Terminal on the 7-segment display (static, negative logic
model) connected to the Output Unit (IR 110) of the Master’s PLC.
The temperature data can be converted to BCD data by using the BCD(024)
instruction (when the temperature data is negative, it can be converted to pos-
itive data using the NEG(160) instruction). For details on using instructions,
Master Unit
DRT1-ID16
Input Terminal
DRT1-OD16
Output Terminal
Switch1 (bit 00)
Indicator (bit 00)
Not used.
Not used.
DRT1-OD16
Not used.
C200HW-DRT21
Not used.
Not used.
IR 50
IR 51
IR 52
IR 53
IR 54
IR 55
IR 56
IR 57
IR 58
IR 59
Output area Input Area
Not used.
DRT1-ID16
Not used.
DRT1-TS04T
C200HW-DRT21
DRT1-232C2
Not used.
IR 350
IR 351
IR 352
IR 353
IR 354
IR 355
IR 356
IR 357
IR 358
IR 359