115
Description of Operation Section 3-2
Online operation from CX-Process
Tool
During
simple
backup
operation
Results on CX-
Process Tool
when operation
is not possible
Backup
continued/
interrupted
Data in Memory Card resulting
from simple backup operation
Download Downloading individual
function block ITEMs
(operation data)
Possible --- Possible Simple backup operation ends
normally, but the data may not be
backed up in the Memory Card.
Data transfer to flash
memory
Possible, but
backup may
not be normal
--- Simple backup operation ends
normally, but the data will not be
backed up in the Memory Card.
Downloading LCU/LCB Possible, but
backup may
not be normal
--- Simple backup operation ends
normally, but the data will not be
backed up in the Memory Card.
Download-
ing individual
function
blocks
System
common
block
Possible --- Simple backup operation ends
normally, but the data will not be
backed up in the Memory Card.
Operation
blocks
Control
blocks
Sequence
control
blocks
Field ter-
minals
Download-
ing user link
tables
Selected
entries
Possible --- Simple backup operation ends
normally, but the data will not be
backed up in the Memory Card.
All entries --- Simple backup operation ends
normally, but the data will not be
backed up in the Memory Card.
Upload Upload new Possible --- Possible Simple backup operation ends
normally.
Update previous Possible --- Simple backup operation ends
normally.
Verification Possible --- Possible Simple backup operation ends
normally.
Deleting registered blocks Possible --- Possible Simple backup operation ends
normally, but the data may not be
deleted in the Memory Card.
Setting operation cycle globally Possible --- Possible Simple backup operation ends
normally, but the data may not be
backed up in the Memory Card.
Operation
commands
Cold start Possible --- Possible Simple backup operation ends
normally.
Hot start Possible --- Simple backup operation ends
normally.
Stop Possible --- Simple backup operation ends
normally.
System operation validation Possible --- Possible Simple backup operation ends
normally.
Action validation Possible --- Possible Simple backup operation ends
normally.
All clear Possible --- Possible Simple backup operation ends
normally.
Tuning Possible --- Possible Simple backup operation ends
normally.

Table of Contents

Other manuals for Omron SYSMAC CS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CS Series and is the answer not in the manual?

Omron SYSMAC CS Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CS Series
CategoryController
LanguageEnglish

Related product manuals