Exchanging Data Using SCADA and Other Software Section 3-4
contain the new value. In this case, the data cannot be read properly.
To be sure that both ITEMs contain the correct data, read the 8-digit
value (such as an accumulated value) two times, compare the two 8-
digit values, and proceed only when the two values are equal.
2. Perform the same processing described above to verify the accuracy of 8-
digit values in the HMI area when reading or writing the values from the
CPU Unit instead of the SCADA Software.
EM Area Allocation
Note CSV Output Functions for HMI Data Allocation Parameters (CX-Process
Tool Ver. 3.2 or Higher)
When CX-Process Tool Ver. 3.2 or higher is used, the HMI data allocation
parameters (indicating which tag or tag ITEM is to be allocated in which
address of the EM Area) can be output in CSV format.
00000 00000 00000
00020 00020 00020
01020
06020
10020
12020
12020
12660 12660 12660
14020 14020 14020
14720 14720 14720
15000 15000 15000
15020 15020 15020
16020
21020
25020
27020 27020
27660 27660 27660
29020 29020
32767 32767 32767
Specified
EM Bank
CS1W-LCB05
CS1D-CPU@@P
System Common 20 words
Send
Control/Operation Block
10,000 words
(Addresses 001 to 500)
Reserved
2000 words
(Addresses 501 to 600)
External Control Block
640 words except for
CS1D-CPU@@P
(Addresses 601 to 632)
Reserved
1,360 words
(Addresses 633 to 700)
System Use
700 words
700 addresses
Reserved
280 words
System Common 20 words
Receive
Control/Operation Block
10,000 words
(Addresses 001 to 500)
Reserved
2000 words
(Addresses 501 to 600)
External Control Block
640 words except for
CS1D-CPU@@P
(Addresses 601 to 632)
Reserved
1,360 words
(Addresses 633 to 700)
Reserved
---
Real PV input value
monitor area
Specified
EM Bank
CS1G-CPU43/44/45P
System Common 20 words
Send
Control/Operation Block
6000 words
(Addresses 001 to 300)
Reserved
6640 words
Reserved
1360 words
System Use
700 words
700 addresses
Reserved
280 words
System Common 20 words
Receive
Control/Operation Block
10,000 words
(Addresses 001 to 300)
Reserved
6640 words
Reserved
1,360 words
Reserved
Send
Real PV input value
monitor area
Specified
EM Bank
CS1W-LCB01
CJ1G-CPU42P
System Common 20 words
Send
Control/Operation Block
1000 words
(Addresses 001 to 050)
Reserved
11,000 words
(Addresses 051 to 600)
External Control Block
640 words (Not supported
by CJ1G-CPU@@P)
(Addresses 601 to 632)
Reserved
1360 words
System Use
700 words
700 addresses
Reserved
280 words
System Common 20 words
Receive
Control/Operation Block
1000 words
(Addresses 001 to 050)
Reserved
11,000 words
(Addresses 051 to 600)
External Control Block
640 words (Not supported
by CJ1G-CPU@@P)
(Addresses 601 to 632)
Reserved
6856 words
(Addresses 633 to 700)
---
---
29520
Send
29320
---
29020
Reserved
29070
---
SendReal PV input value
monitor area

Table of Contents

Other manuals for Omron SYSMAC CS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CS Series and is the answer not in the manual?

Omron SYSMAC CS Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CS Series
CategoryController
LanguageEnglish

Related product manuals