209
Description of FINS Commands Section 6-3
Response code
Response code Meaning
0000 Hex Normal completion
1001 Hex Command length over
• The command length exceeds 2002 bytes.
1002 Hex Insufficient command length
• The command length is less than six bytes.
1003 Hex Number of elements/number of data mismatch
• The number of data items does not match the number of
ITEMs.
1101 Hex No type
• An unusable block address was specified in the parameter
type.
• The block address specified in the parameter type is an
unregistered function block.
• Function blocks other than System Common blocks cannot
be accessed as the RAM has not yet been initialized
(cleared) after a battery failure causes content of RAM to be
lost.
1103 Hex Specified address out-of-range error
• The start address contains a non-existent ITEM.
• An attempt was made to write to the format setting of a Sys-
tem Common block.
110C Hex Other item parameter error
• Number of ITEMs is 0.
• The specified data length does not match the actual data of
each ITEM specified by the write start address.
• The combination of block address and block format is forbid-
den.
• Write data is out of the data range for each ITEM.
2605 Hex Service in operation
The function block data in the Loop Controller was replaced,
and then the LCB started operation without restarting the LCB
restart or cycling the PLC power supply. (An attempt was
made to write 1 or 2 to the System Common Block ITEM 014