Description of FINS Commands Section 6-3
5) Detailed information
Indicates the detailed information of the error. For details on error codes, see
7-1 Errors and Alarm Troubleshooting.
6) Minutes, seconds, day, hours, year, month
All values are expressed in BCD (Binary-Coded Decimal). The time data is
read from the CPU Unit.
Response code
Note When there is no error log data for the number of read records, the records
currently stored are read, and 0000 Hex (normal completion) is taken as the
response code.
Item Range
Minute 0 to 59
Second 0 to 59
Day 1 to 31
Hour 0 to 23
Year 0 to 99 (lower 2 digits)
Month 1 to 12
Response code Meaning
0000 Hex Normal completion
1001 Hex Command length over
• The command length exceeds six bytes.
1002 Hex Insufficient command length
• Command length is less than six bytes.
1103 Hex Specified address out-of range error
• The read start record No. was specified for the number of
currently stored records or more. (excluding 0000 Hex)
110C Hex Other item parameter error
• Number of read records is 0.