Unit Number Switches
3-1SectionNames and Functions of Parts
23
Unit number Words allocated from
Special I/O Unit Area
Words allocated from
DM Area
0 CIO 2000 to CIO 2009 D20000 to D20099
1 CIO 2010 to CIO 2019 D20100 to D20199
2 CIO 2020 to CIO 2029 D20200 to D20299
3 CIO 2030 to CIO 2039 D20300 to D20399
4 CIO 2040 to CIO 2049 D20400 to D20499
5 CIO 2050 to CIO 2059 D20500 to D20599
6 CIO 2060 to CIO 2069 D20600 to D20699
7 CIO 2070 to CIO 2079 D20700 to D20799
8 CIO 2080 to CIO 2089 D20800 to D20899
9 CIO 2090 to CIO 2099 D20900 to D20999
10 CIO 2100 to CIO 2109 D21000 to D21099
... ... ...
n CIO 2000 + (n × 10) to
CIO 2000 + (n × 10) + 9
D20000 + (n × 100) to
D20000 + (n × 100) + 99
... ... ...
95 CIO 2950 to CIO 2959 D29500 to D29599
Note If the same unit number that is used for another Special I/O Unit is set, a Unit
Number Duplication Error (fatal error) will occur in the CPU Unit (“UNIT No. DPL
ERROR” displayed at Programming Console), and the PC will not operate.
A40113 in the CPU Unit will turn ON.
Turn ON this switch to enable Programming Device servicing at the peripheral
port and turn it OFF to disable it. Operational errors related to the connection of a
Programming Device (such as changes in the operating mode) can be pre-
vented by turning OFF this switch.
Programming Device connection
switch
Programming Device
Set to ON:
TOOL
ON OFF
Connection enabled
(The switch must be turned ON to use a
Programming Device.)
Set to OFF:
TOOL ON OFF
Connection disabled
(Turn OFF the switch to prevent
operational errors.)
Note 1. If the switch is turned OFF, Programming Device servicing is not performed
and so the scan time is shorter.
2. This switch can also be used as a restart switch for connection with the Pro-
gramming Device.
The peripheral port is used for connecting to a Programming Device (i.e., a Sup-
port Software installed on a computer or a Programming Console).
Note The Unit automatically recognizes the serial communications mode (i.e., Pro-
gramming Console bus, peripheral bus).
The I/O connector is for contact I/O. Make a cable for this connector with the
24-pin connector provided with the Unit. (For details, refer to 3-3 Wiring.)
The special I/O connector is for special I/O: Pulse inputs and pulse outputs for
the CS1W-HCP22, and pulse inputs and analog outputs for the CS1W-HCA22.
Either make a cable for this connector with the 40-pin connector provided with
the Unit, or using a special OMRON cable, connect to an OMRON Connector
Terminal Conversion Unit. (For details, refer to 3-3 Wiring.)
Programming Device
Connection Switch
Peripheral Port
I/O Connector
(All Units)
Special I/O Connector
(CS1W-HCP22/HCA22
Only)