4-3SectionWords Allocated in DM Area
50
4-3-2 DM Area Allocation Details
Initial Setting Area (m to m+9)
Word Bits Function
Contents
Setting
Condition
m 00 to 07 RUN/STOP
command
enable/disable
and operating
d
g
Operating mode
at startup
Operating mode
specification after
startup
Operation for
error at PC
(SR 24915 turns
ON)
g
mode at
startup
00 Hex RUN/STOP
command
enabled
Determined by the status of the
RUN/STOP Command Bit (n, bit 00).
The operating mode can be switched
between RUN mode and MONITOR
mode using the Programming Device
connected to the Customizable
Counter Unit.
The RUN/STOP
Command Bit (n,
bit 00) turns OFF
and Customizable
Counter Unit
operation stops.
Note: There are
errors for which
the RUN/STOP
Command Bit
may not turn OFF.
For details, refer
to 9-3
Troubleshooting
Tables.
01 Hex
RUN/STOP
command
disabled
Determined by
the operating
mode
specification of
the Programming
Console.
Note: If there is
no Programming
Console
connected or if
the Programming
Device
connection switch
on the front of the
Unit is set to OFF,
the mode is
automatically set
to RUN mode.
Determined by
commands from
the Programming
Device (CX-
Programmer or
the Programming
Console).
Note: The
RUN/STOP
command (n, bit
00) is disabled.
Customizable
Counter Unit
operation
continues.
02 Hex PROGRAM mode
03 Hex MONITOR mode
04 Hex RUN mode
08 to 15 (Reserved by system.) ---

Table of Contents

Other manuals for Omron SYSMAC CS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CS1 and is the answer not in the manual?

Omron SYSMAC CS1 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CS1
CategoryController
LanguageEnglish

Related product manuals