D-100 Display Module BACnet Installation and Operation Guide 04/12 - 0635-2 Page 25
Reported Problem Possible Solutions
Network communications are disrupted
when the device is connected (cont.).
• Shielddrainconnectionsshouldbedaisy
chained in the same manner as the
signal cables for RS485. The shield drain
wire should be left unterminated at the
end of the cable and connected to earth
only at the network master controller.
Shield wires must not be connected to the
RS485 connector on the D-100.