Environmental Requirements
method. Ensure that the facility administrator or qualified electrical engineer who verifies the
grounding method for the building performs the grounding work.
Environmental Requirements
The following table lists the temperature, humidity, and altitude specifications, as well as
acoustic noise, vibration, and shock specifications.
TABLE 6
Environmental Specifications
Specification Operating Nonoperating
Ambient temperature (Does
not apply to removable media)
Maximum range: 41°F to 95°F (5°C to 35°C) up to 2,953
feet (900 meters)
Optimal: 69.8°F to 73.4°F (21°C to 23°C)
Note - Maximum ambient operating temperature is derated by
1 degree C per 300 meters of elevation beyond 900 meters, up
to a maximum altitude of 3,000 meters.
–40°F to 154°F (–40°C to 68°C)
Relative humidity 10% to 90% noncondensing, short term 23°F to 113°F (–
5°C to 55°C)
5% to 90% noncondensing, but not to exceed 0.024 kg of
water per kg of dry air (0.053 lbs water/2.205 lbs dry air)
Up to 93% noncondensing 95°F (35°C)
maximum wet bulb
Altitude Up to 9,840 feet (3,000 meters)
Note - In China markets, regulations may limit installations to
a maximum altitude of 6,562 feet (2,000 meters).
Maximum 39,370 feet (12,000  meters)
Acoustic noise Maximum condition: 7.1 Bels A weighted
Idle condition: 7.0 Bels A weighted
Not applicable
Vibration 0.15 G (z-axis),
0.10 G (x-, y-axes), 5-500Hz swept sine
IEC 60068-2-6 Test FC
0.5 G (z-axis),
0.25 G (x-, y-axes), 5-500Hz swept sine
IEC 60068-2-6 Test FC
Shock 3.5 G, 11 ms half-sine
IEC 60068-2-27 Test Ea
Roll-off: 1.25-inch roll-off free fall,
front to back rolling directions
Threshold: 13-mm threshold height at
0.65 m/s impact velocity
ETE-1010-02 Rev A
Set conditions to the optimal temperature and humidity ranges to minimize the chance of
downtime due to component failure. Operating the Oracle Server X6-2 for extended periods at
or near the operating range limits, or installing it in an environment when it remains at or near
nonoperating range limits could significantly increase hardware component failure. See also:
20 Oracle Server X6-2 Installation Guide • July 2020

Table of Contents

Other manuals for Oracle Server X6-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Oracle Server X6-2 and is the answer not in the manual?

Oracle Server X6-2 Specifications

General IconGeneral
BrandOracle
ModelServer X6-2
CategoryServer
LanguageEnglish

Related product manuals