IG-150-EN version 04; 03/10/16
52
Unit configuration General instructions
ekor.rps
3.6. Other configuration settings
Only accessible by keyboard/display, on “CHANGE
SETTINGS”, “PROG. TABLE 0”, “DEFINE PROTECT.. They are the
following:
3.6.1. Frequency
It can be 50 Hz or 60 Hz. It is a fundamental protection
setting. If it is not the correct one, the measurements and,
therefore, the protection operation will be wrong.
3.6.2. Language
It can be English or Spanish. It relates to the texts shown
ondisplay.
3.6.3. Phase order
It can be A, B, C or C, B, A. It aects only to the protection
functions of broken conductor and unbalance (currents and
voltages). To verify that the order corresponds to the wiring,
check in “measurements that the ratio of the inverse/direct
component is close to 0 %, when introducing 3 balanced
currents of about 1 A.
3.6.4. Neutral Parameter
If it is “by transformer indicates that an input transformer
exists to measure the zero sequence voltage; if it is “measured”
indicates that it must be calculated as a vectorial sum of the
simple phase to ground voltages.
3.6.5. Calibration
This menu position is exclusively to be used by the
Ormazabal's technical-commercial department, according
to a certain procedure. It should not be used by the user.
3.6.6. Test mode
The test mode is to be used by Ormazabals technical–
commercial department exclusively, following a specic
procedure. It must not be used by the user.