Reassembly
32 900-0054-01-00 Rev A
Syst em Funct ional Test
Perform a Funct ional Test as follows before put t ing t he syst em back into full service.
1.
Reinst all FLEXmax Charge Cont roller back int o t he syst em.
2.
Initially apply only battery power to the FLEXmax controller.
3.
The display should “boot up” and the soft keys should function properly. Test t he soft keys by
cycling through the menus.
4.
Once proper operation is verified, apply PV input to the FLEXmax Charge Controller to
resume charging.
5.
Using a digital multimeter, test the applicable test points to confirm proper volt age levels as t hey
are applied to the system.
6.
Replace all t he appropriat e component covers and secure t he system for official use by the
cust omer.
If t he unit does not perform as expect ed or fails t he Funct ional Test , disconnect al l p ower sources
(i.e. open all breakers or disconnect s) and cont act Out Back Technical Support for addit ional assist ance.