Data setting
value
Details
0
Retry function disabled(Retry is not carried out)
1
Execute retry only for overcurrent fault and heat sink fin abnormal
overheating(SC1,2,3. OC 1,2,3)
2
Execute retry only for overvoltage fault(OU1,2,3).
3
Execute retry for overcurrent fault and heat sink fin abnormal heating
(SC1,2,3. OC 1,2,3)and overvoltage fault(OU1,2,3).
[Parameter P26: Retry selection setting]
Data setting range(times)
1 to 10
[Parameter P27: Retry times setting]
LOWER and UPPER FREQUENCY CLAMP(Parameter P28 and P29)
Used to set the lower and upper limits of the output frequency.
Data setting range(Hz)
Setting unit (Hz)
0.5 to 250
0.10.5 to 100Hz 1100 to 250Hz
[Parameter P28:
Lower frequency clamp setting]
[Parameter P29:
Upper frequency clamp setting]
Note1) If the upper frequency clamp is lower than the maximum output frequency
(Parameter P14), the upper frequency clamp will have the priority.
Note2) If the lower frequency clamp is higher than the upper frequency clamp, the upper
frequency clamp will have the priority.
MONITOR SELECT and LINE SPEED MULTIPLIER
(Parameter P30 and P31)
Used to select the details of the operation panel's main display.
Data setting
value
Details displayed on
operation panel
Output frequency
0
Line speed
[Parameter P30:
Monitor details selection]
[Parameter P31:
Line speed multiplier setting]
Used to set the multiplier with respect to the
output frequency when the line speed is displayed
on the operation panel's main display.
Example : Display line speed
Line speed(m/min)= F(Hz) X K(multiplier)
䊶To display the line speed 25(m/min) for 50Hz, set the multiplier(K) to "0.5".
Note) A line speed exceeding "999" is displayed as "9.9.9.".
(The 4-pole motor speed cannot be displayed.)
52
1
0.1 to 100(can be set in 0.1 units)
Data setting
range