65
Operation is carried out as fault CLOSE command signal.
2
When CLOSE command signal is ON, and safety sensor
signal is ON, fault CLOSE operation iscarriedout.
1
When safety sensor signal is ON, fault OPEN operation is
carried out.
0
Functions
Setting data
value
Function select of safety sensor signal in control input terminal No.5 may be carried out.
䇼When data value is set to be 0䇽
After safety sensor signal is ON, OPEN operation is forced to becarried out by
the door in virtue of obstacle detect function. Response time of safety sensor
signal may be set with Parameter P44.
䇼When data value is set to be 1䇽
In the state that CLOSE command signal is ON, after safety sensor signal is ON,
fault CLOSE operation is carried out by the door. In case of no CLOSE command
signal, no fault CLOSE operation will be carried out even if safety sensor signal is ON.
䇼When data value is set to be 2 䇽
Control input terminal No.5 serves as fault CLOSE command signal.
When fault CLOSE command signal is ON, fault CLOSE operation will be carried
out. Only with fault CLOSE command, fault CLOSE operation will be carried out.
Priority order of the three run commands (OPEN command, CLOSE command
and fault CLOSE command) is as follows. When all of the three signals are ON
simultaneously, note that operation will becarried out according to the following
priority order.
䋾䋾
(Note) When fault CLOSE operation is being carried out in CLOSE operation
region, and fault CLOSE command signal is OFF (OPEN command and CLOSE
command are both OFF), note that operation will be different due to setting value
of Parameter P75 ( stop select in OPEN/CLOSE operation).
OPEN
command
fault
CLOSE
command
CLOSE
command
About fault CLOSE operation
䊶In the event that signal input in control input terminal No.5 (parameter 80 is 䇸1䇹or 䇸2䇹)
is ON, fault CLOSE operation is carried out according to frequency and acceleration /
deceleration time in fault CLOSE operation.
䊶Hold operation is identical to CLOSE hold operation.
䊶In fault CLOSE operation, OPEN operation is carried out when OPEN command is
ON.
䊶In fault CLOSE operation, obstacle detect (time, slip and current) is still effective.
䊶Obstacle detect conducted in fault CLOSE operation, its setting value is that of
parameter 81: forced OPEN operation judgment time in fault CLOSEoperation.
䊶When RY1䊶2䊶3function select (P48䌾P50䋩䋽6䇮r6, , obstacle detect signal is set
to be ON in fault CLOSE operation.
Parameter P80: Safety sensor function select