Display
OPEN arrival signal and CLOSE
arrival signal are both turned ON.
En4
When door position data is OPEN arrival
state, there is no arrival signal.
En5
When door position data is CLOSE arrival
state, there is no arrival signal.
CPU
Excessive noise applied on the inverter
Reduce the noise around the inverter.
Check the OPEN arrival signal and
CLOSE arrival signal
En1 There is no encoder pulse
Check the encoder's power supply
Check the encoder's wiring
Details and cause of fault Remedies
The rotation direction of the encoder
pulse is different from the rotation
direction of a command
Check the encoder's wiring
(phase A and phase B)
Check the OPEN arrival signal.
Check the CLOSE arrival signal
Note) Refer to " Troubleshooting ķ and ĸ " on page 91 and 92.
Resetting Fault Trips
If a fault is displayed on the operation panel's main display and the inverter is
stopped, remedy the fault before resetting. It is possible to restart the inverter
after resetting.
Power
reset
Turn OFF the power once, then turn it ON again.
(Operation can be started when the power is turned ON again.)
Resetting
by stop
signal
When operation is set to local (Parameter P08 set to "0" or "1"), the fault
will be reset when the "STOP button" on the operation panel is pressed.
When operation is set to external ( Parameter P08 set to "2"), the fault
will be reset when both the OPEN/CLOSE signal are turned OFF.
When operation is set to communication ( Parameter P08 set to "3"),
the fault will not be reset even if the operation command of communication
is turned OFF. In case of communication setting, the fault will be reset with
"fault reset command".
Resetting
by panel
The fault will be reset when the "STOP button" on the operation panel
is pressed.
Depending on the start mode function setting, if the fault trip is reset
with inputting the run signal, the inverter may restart suddenly.
(Reset the trip after ensuring personal safety.)
Failure to do so could lead to injury.
Caution
90
En2
En3