DOC-0017-04-EN: AC20 Series - Hardware Installation Manual 
  DOC-0017-04-EN-A 22.03.2023   101 (154) 
 Application ‘2’: Auto / Manual 
Two Run inputs and two Setpoint inputs are provided. The Auto/Manual switch selects which pair of inputs 
is active. 
The Application is sometimes referred to as Local/Remote. 
 
 
 
110-230Vac (or 24Vdc) voltage supply 
Healthy: Relay output (to lamp) 
Motor Thermistor ‘+’ connection 
Motor Thermistor ‘-’ connection 
‘Manual’ Remote Setpoint (%): 0-10V variable input (from potentiometer) 
‘Auto’ Remote Setpoint (%): 4-20mA variable input (from current source) 
Speed Demand (%): 0-10V variable output (to voltmeter) 
Value = 100%: 0-10V variable output (+10V fixed reference voltage) 
‘Manual’ Run: 24V digital input 
‘Auto’ Run: 24V digital input 
Auto / Manual Select: 24V digital input 
Remote Reverse: 24V digital input 
Not Coast Stop: 24V digital input 
STO DISABLED (drive operational) 
 
 
 
 
S