9 Basic Drive Operation
9.1 ‘Local’ Operation
To run the drive using either the onboard keypad, or the 6901 remote keypad, the following steps need to
be followed.
Note: This sequence assumes that the power connections (ac line supply & motor output
connections) have already been connected as per the installation instructions.
Minimum Connections
The minimum control connections required to run the drive in ‘Local’ mode, are shown below.
Note that if Vector Control: Encoder Feedbackcontrol mode is selected, then the motor encoder will
also need to be wired into the Encoder Feedback option card, as detailed previously.
The motor thermistor needs to be connected (or linked out), and the STO function needs to be disabled i.e.,
drive operational.
Configuration Setup:
TH1
Motor Thermistor ‘+’ connection (link to TH2 if no motor thermistor fitted)
TH2
Motor Thermistor ‘-’ connection
STO
STO DISABLED (drive operational)