EasyManua.ls Logo

Parker AC20 Series - 3Ø, 400 V Products; Control Board Ratings; Analogue Inputs

Parker AC20 Series
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DOC-0017-04-EN: AC20 Series - Hardware Installation Manual
140 (154) DOC-0017-04-EN-A 22.03.2023
3ø, 400V Products
DC Link Brake Switch Threshold = 764V
Frame
Size
Product Code
Motor
Power
(kW)
Continuous
Peak (Instant)
Min
Resistor
Value
(Ω)
Brake
Current
(A)
Power
Diss
(kW)
Brake
Current
(A)
Power
Diss
(kW)
2
20G-42-0040...
1.5
2.0
1.5
8.0
6.1
95
20G-42-0065...
2.2
2.9
2.2
8.5
6.5
90
20G-42-0090...
4
5.2
4.0
8.5
6.5
90
3
20G-43-0120...
5.5
7.2
5.5
8.5
6.5
90
20G-43-0170...
7.5
8.5
6.5
8.5
6.5
90
4
20G-44-0230...
11
14.4
11.0
15.3
11.7
50
20G-44-0320...
15
19.6
15.0
25.5
19.5
30
5
20G-45-0380...
18.5
24.2
18.5
25.5
19.5
30
20G-45-0440...
22
25.5
19.5
25.5
19.5
30
20G-45-0600...
30
30.6
23.3
30.6
23.3
25
6
20G-46-0750…
37
48.4
37.0
54.6
41.7
14
20G-46-0900…
45
54.6
41.7
54.6
41.7
14
7
20G-47-1100…
55
54.6
41.7
54.6
41.7
14
20G-47-1500…
75
69.5
53.1
69.5
53.1
11
8
20G-48-1800…
90
109.1
83.3
109.1
83.3
7
20G-48-2200…
110
109.1
83.3
109.1
83.3
7
20G-48-2650…
132
172.8
132.0
191.0
146.0
4
9
20G-49-3200…
160
209.4
160.0
254.7
194.6
3
10
20G-410-3600…
180
235.6
180.0
254.7
194.6
3
Note: Peak (Instant) = Maximum 20sec, 30% ‘on’ duty (except where this value is the same as the
continuous rating)
13.4 Control Board Ratings
Analogue Inputs
Terminal Idents:
Type:
- ± 10V
- 0 10V
Current Modes:
- 0 20mA
- 4 20mA (with wire break detection)
Maximum Input Voltage:
Input Impedance:
Current Mode: <5.5V drop @ 20mA
Resolution:
Isolated:
Overcurrent Protection:
Sample / Update Rate:

Table of Contents

Other manuals for Parker AC20 Series

Related product manuals