EasyManua.ls Logo

Parker AC20 Series - 3Ø, 400 V Products; Calculation

Parker AC20 Series
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DOC-0017-04-EN: AC20 Series - Hardware Installation Manual
62 (154) DOC-0017-04-EN-A 22.03.2023
3ø, 400V Products
Frame
Size
Product Code
Motor
Power
(kW)
Inductance
(mH/phase)
Rated Current
(A)
Peak Current
@150% HD
Rating (A)
2
20G-42-0040...
1.5
4.411
5
11
20G-42-0065...
2.2
2.940
7.5
16
20G-42-0090...
4.0
2.005
11
23
3
20G-43-0120...
5.5
1.575
14
30
20G-43-0170...
7.5
1.192
19
39
4
20G-44-0230...
11
0.919
24
51
20G-44-0320...
15
0.604
37
77
5
20G-45-0380...
18.5
0.501
44
93
20G-45-0440...
22
0.432
51
108
20G-45-0600...
30
0.315
70
148
6
20G-46-0750…
37
0.276
80
170
20G-46-0900…
45
0.235
94
199
7
20G-47-1100…
55
0.184
120
255
20G-47-1500…
75
0.138
160
339
8
20G-48-1800…
90
0.116
190
403
20G-48-2200…
110
0.098
225
477
20G-48-2650…
132
0.080
275
583
9
20G-49-3200…
160
0.067
330
700
10
20G-410-3600…
180
0.060
370
785
Notes:
- AC Line Choke inductance values calculated @400V, 50Hz / 480V, 60Hz
- AC Line Choke impedance is nominally 3% of drive rating
- AC Line Choke maximum voltage rating should be 480V +10%, TN/IT
- AC Line Choke frequency of operation is 50 – 60Hz
- AC Line Choke inductance during 150% overload operation should be >90% of its nominal value
Calculation
The choke ratings listed above are for guidance only. Customers may want to calculate their own ratings
using the formulas below:
1ø Products:
=
󰇡 ×
100
󰇢

÷
(
2 × 
)
Where:
L
= Inductance/phase (H)
Vin
= Line-to-Neutral Input Voltage (V)
Z
= AC Line Choke Impedance (%)
Iin
= Rated Input Current (A)
fin
= Mains supply frequency (Hz)

Table of Contents