DOC-0017-04-EN: AC20 Series - Hardware Installation Manual
DOC-0017-04-EN-A 22.03.2023 99 (154)
- Select an ‘Application’ (Macro) by changing the value of the ‘Applicationparameter.
- Next, change the ‘Load Application’ parameter FALSE’ to ‘TRUE.
Parameter Name
No.
Default Value
Range
Units
Type
Writable
Application
1150
9: Saved
0: Null
1: Standard
2: Auto/Manual
3: Presets
4: Raise/Lower
5: PID
6: Aux Comms
9: Saved
ENUM
STOPPED
Application Lock
1152
FALSE
BOOL
ALWAYS
Load Application
1151
FALSE
BOOL
STOPPED
- To ‘lock’ the application so it can not be accidently changed, set the ’Application Lockparameter
from ‘FALSE’ to ‘TRUE’.
Running The Drive
Providing the drive is:
1. Set to ‘Remote’ operating mode.
2. Initial Drive Setup’ has been completed.
3. An ‘Autotune’ routine has been completed (if set to SVC mode).
The drive is ready to be run from the remote switches (see application examples below):