EasyManua.ls Logo

Parker AC20 Series - Page 42

Parker AC20 Series
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DOC-0017-04-EN: AC20 Series - Hardware Installation Manual
42 (154) DOC-0017-04-EN-A 22.03.2023
Recommended Wire & Ferrule Sizes
The following wire sizes and ferrules are recommended for use with the control board terminal blocks:
Wire Type
Maximum
Wire Size Ferrule Details
Bare Wire / Ferrule
Length
Stranded
1x 1.0mm
2
(1x 18 AWG)
None Fitted
5mm
(0.20”)
2x 0.5mm
2
(2x 21 AWG)
None Fitted
Stranded
1x 0.75mm
2
(1x 19 AWG)
White Collar,
1.5mm OD
6mm
(0.24”)
1x 0.5mm
2
(1x 21AWG)
Orange Collar, 1.3mm
OD
Terminal Block Tightening Torque
The control board terminals should be screwed to a maximum torque as specified below:
Screw Head
Terminal Tightening Torque
M2, Flat
0.19 Nm
(1.7 Lb-in)
Cable Saddles (Frames 6 10)
On Frames 6 10, 3x cable saddles have been provided to help with the routing of the control and
communications cables inside the products, for example:

Table of Contents