6.3.2 Basic programming mode chart 742F-762F/293 valve type
Parameter
description
Range of
values
Default
value
Units of
measure
Notes
Program valve
type
255, 263, 268,
278 and
Magnum series
None N/A -
Program system
size
5 - 100 / F None liters -
Time setting 1:00 - 12:59AM
0:00 - 23:59PM
12:00PM hour:
minute
-
Day of week N/A None N/A -
Time of backwash 1:00 - 12:59AM
0:00 - 23:59PM
12:00PM hour:
minute
Dependent of time setting (AM or
PM).
Days override
(762F controller
only)
0.5 - 99 0 day 0 = no days override.
0.5 = regeneration twice a day at
time of regeneration and 12 hours
later.
Days between
regeneration
(742F controller
only)
0.5 - 99 0 day 0 = no days between regeneration.
0.5 = regeneration twice a day at
time of regeneration and 12 hours
later.
Backwash length 0 - 200 14 minute -