Installer manual Autotrol Magnum 293 - 298 Logix 742-762 - Programming
54 / 110 Ref. MKT-IM-012 / D - 03.02.2022
6.3.4 Basic programming 742F - 762F/293 valve type
6.3.4.1 Program valve type
Set your valve type through the options.
1. Use and to scroll though valve type choices.
ð Valve type flashes
2. Choose the 293 valve type.
3. Press to validate the system size selected and advance to
the next parameter using or .
6.3.4.2 Program system size
Set your system in filter configuration.
1. Use and to scroll though resin volume choices.
ð Three dashes than resin volume flashes.
2. Select "F" to validate the system as a filter configuration.
3. Press to validate the system size selected and advance to
the next parameter using or .
4. If an incorrect setting is programmed, see Resetting the
controller [
→
Page62].
6.3.4.3 Time setting
Set the current time.
1. Press when the time of the day is displayed.
ð Time flashes.
2. Adjust displayed time with and .
3. Press to validate the selection and advance to the next
parameter using or .
6.3.4.4 Day of week
Set the current day of the week.
1. Press .
ð Arrowflashes.
2. Adjust displayed time with and .
3. Press to validate the selection and advance to the next
parameter using or .