Installer manual Autotrol Magnum 293 - 298 Logix 742-762 - Programming
56 / 110 Ref. MKT-IM-012 / D - 03.02.2022
6.4 Advanced programming
Info
Press and hold + for 5 seconds to access advance programming.
A "P" symbol is displayed on the bottom left of screen
6.4.1 Basic programming parameters (5 - Cycle softener system)
Parameter
description
Range of
values
Default
value
Units of
measure
Notes
P1 Time of day 1:00 - 12:59
AM
0:00 - 23:59
PM
12:00 PM Hour :
minute
Range depends on value
selected for P10.
P2 Day of week N/A None N/A -
P3 Time of
regeneration
1:00 -
12:59AM
0:00 -
23:59PM
2:00 AM Hour:
minute
Range depends on value
selected for P10.
P4 Calendar
override
0 - 99 3 Days 0 = no calendar override.
0.5 = regeneration twice a day at
time of regeneration and
12hours later.
Calendar override skipped if at
least one day of regeneration
selected.
P5 Day of week
regeneration
N/A None N/A Day of week regeneration is
skipped if calendar override is
more than 0 (742 controller
only).
P6 Salt setting 50 - 290 110 g/l Unit of measure depends on
value selected for P9.
P7 Capacity of unit 0.1 - 90 * kg Unit of measure depends on
value selected for P9.
P8 Hardness of
water
30 - 2000 400 g/l Unit of measure depends on
value selected for P9
(762controller only).
*Calculated depending on salt setting and resin volume. The capacity may be manually adjusted.