Installer manual Autotrol Magnum 293 - 298 Logix 742-762 - Programming
Ref. MKT-IM-012 / D - 03.02.2022 59 / 110
Parameter
description
Range of
values
Default
value
Units of
measure
Notes
P12 Remote
regeneration
3 - 250 60 Second Time remote switch must be
active to start regeneration on
742 controller.
P13 - - - - Skipped for 3 - cycle filter
configuration.
P14 - - - - Skipped for 3 - cycle filter
configuration.
P15 - - - - Skipped for 3 - cycle filter
configuration.
P16 Reserve type 0 - 3 0 N/A 0 = variable reserve delayed
regeneration.
1 = fixed reserve delayed
regeneration.
2 = variable reserve immediate
regeneration.
3 = fixed reserve immediate
regeneration.
P17 Initial average or
fixed reserve
0 - 70 30 % of capacity Depends on value selected for
P16.
P18 Flow sensor
select
0 - 5 * N/A 0 = internal Magnum NHWB.
1 = 1" Autotrol turbine.
2 = 2" Autotrol turbine.
3 = User defined.
K-factor,
4 = User defined pulse
equivalent.
5 = internal Magnum HWB.
P19 K-factor or pulse
equivalent
1.00 -99.99
0 - 9999
0.01
1
N/A K-factor P18 = 3.
Pulse equivalent P18 = 4.
* Default value selected with valve type and resin volume.
** Factory default value is "0" for North America and "1" for World units.
Info
Parameters P16 to P19 are skipped on 742 controller.