Installer Manual Foleo - Installation
Ref. MKT-IM-038 / C - 15.11.2019 27 / 112
4.3.4. Mechanical
CAUTION
Do not over-tighten the pipe to piping boss.
CAUTION
Do not put excessive force on the inlet, outlet or drain connections of the valve.
PROHIBITION
Use of silicone or petroleum-based lubricants, oils or hydrocarbon-based lubricants, is
strictly prohibited with Foleo 5800 XTR as the valve 5800 is equipped with silicone o-rings
that are not compatible with silicone based lubricant.
MANDATORY
Use only P-80
®
Emulsion lubricant (water based lubricant). Using another lubricant may
damage the valve.
all plastic connections should be hand tightened. PTFE (plumber’s tape) may be used on
connections that do not use an o-ring seal. Do not use pliers or pipe wrenches;
all plumbing must be completed according to local codes;
soldering near the drain line should be done before connecting the drain line to the valve.
Excessive heat will cause interior damage to the valve;
observe the drain line requirements:
maximum 1 m high at 2 bars inlet pressure. Add 50 cm for additional 1 bar at the softener’s inlet;
do not use lead-based solder for sweat solder connections;
the valve is designed for minor plumbing misalignments. Do not support the weight of the
system on the valve fittings, plumbing, or the bypass;
it is not recommended to use sealants on the threads. Use PTFE (plumber’s tape) on the threads
of the 25.4 mm (1") NPT elbow, the drain line connections, and other NPT/BSP threads.
4.4. Integration constraints
Location of a water treatment system is important. The following conditions are required:
CAUTION
The surface for installation (platform or floor) must be solid, flat and level.
MANDATORY
Drain must be capable of handing a maximum backwash flow rate of 19 L/min.
locate the softener as close as possible from drain discharge point and within 12.2 m maximum
of drain discharge point, respecting minimum drain line diameter advises given at chapter
4.5.7. Drain line connection, page 35;
room to access equipment for maintenance and adding salt in the brine tank;
constant electrical supply to operate the controller;