Installer Manual Foleo - Programming
54 / 112 Ref. MKT-IM-038 / C - 15.11.2019
5.4.3. Valve screen
From the main master settings screen press the valve button to display the valve screen.
system: Displays the system type. Type 4 (single system) is currently the only available selection.
valve: Set to 5800.
regen type: Set to softener metered delayed.
Press to save and pass to the next screen or press to return to the master settings screen
without saving.
media volume: Set to 10L, 15L, 20L or 28L, respectively for Foleo 10, Foleo 15, Foleo 20 and
Foleo 30.
salt dosage: Adjust the salt dosage from 80 to 200 mg/L, depending of hardness water outlet desired.
blfc size: BLFC size set to 0.500 gpm as standard. For Foleo 10 and 15 models, set to 0.125 gpm. For
Foleo 20 and 30 models, set to 0.25 gpm.
Press to save and pass to the next screen or press to return to the master settings screen
without saving.
Valve
valve
regen type
4
5800
softener
mtr.delayed
system
Valve
salt dosage
blfc size
10
L
80
g/L
0.500
gpm
media volume