EasyManuals Logo

Pfeiffer Vacuum OBC V4 User Manual

Pfeiffer Vacuum OBC V4
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
8.3 Control via the REMOTE connector
NOTICE
Safety of Extra-Low Voltage circuits
Remote control circuits are equipped with dry contact outputs (24 V - 1 A max). Overvoltages and
overcurrents can result in internal electrical damage. Users must observe the following wiring condi-
tions:
Connect these outputs in accordance with the rules and protection of Safety Extra-Low Voltage
(SELV) circuits.
The voltage applied to these contacts should be less than 24 VDC and the current less than 1 A.
Description
Connection via the REMOTE connector (HD, 15-pin D-Sub female) can be used for:
remote control of following functions: start, stop, purge, and air inlet
remote pump status through auxiliary dry contacts
The remote control mode is active when the ‘Remote hardware’ control mode is set on the RS-232/
RS-485 serial link or via the HHR unit.
When the ‘Remote hardware’ control mode is set, the Stand-by speed and temperature setpoint can be
set via the RS-232/RS-485 serial link or the HHR unit.
Use shielded cable and connect both sides to the ground.
8.3.1 Logic input wiring
Control by direct voltage
The inputs are active when a DC voltage between 10 and 24 VDC is applied between their pins (wiring
customer supplied).
5 4 3 2
1
6
1115
10 9 8
7
+-
+
+
+
10-24 VDC
S
5
(+)
(-)
15
10
5
(+)
(-)
GND
15
10
11, 12, 13, 14
A B
+15 V
Fig. 6: Remote connector: control by direct voltage
A Internal wiring B Wiring from customer's side
Voltage
10-24 VDC
Function
S1 (11-15)
Purge
1)
Contact closed: the purge solenoid valve is activated.
Contact open: the purge solenoid valve is not activated.
S2 (12-15)
Venting
1)
Contact closed: the air inlet solenoid valve is activated.
Contact open: the air inlet solenoid valve is not activated.
S3 (13-15)
Stand-by
1)
Contact closed: Stand-by speed is selected.
Contact open: pump rotation speed is the pump nominal
speed.
S4 (14-15)
Start/Stop pump
1)
Contact closed: the pump starts.
Contact open: the pump stops.
1) This function runs when the control mode is set to ‘Remote hard’ via the RS-232/RS-485 serial link (see chapter “List of
commands”) or via HHR (see chapter “SETUP menu”).
Interfaces for control
34/60

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pfeiffer Vacuum OBC V4 and is the answer not in the manual?

Pfeiffer Vacuum OBC V4 Specifications

General IconGeneral
BrandPfeiffer Vacuum
ModelOBC V4
CategoryDC Drives
LanguageEnglish

Related product manuals