PEC Plus user manual Appendix C: Factory defaults
31040003 83
Appendix C: Factory defaults
When your PEC Plus leaves the factory, it comes with default settings and configuration. When you
configure and set up your PEC Plus, you change its settings.
Resetting your PEC Plus erases all the configuration and settings you programmed and then restores
the settings to what they were when the control left the factory. For more information, read
Restoring the factory defaults on page 69.
The table below lists the factory defaults.
Configuration Alarm settings
Relays 1 to 6
Variable stages 1 and 2
Temperature units
Probe 1
Probe 2
Probe 3
Probe 4
Security
Hysteresis
Off ¹
Off
°F
On
Off
Off
Off
Off
1.0
¹ If the actuator present pins are in place, the
defaults for the relays are:
RLY1 – actuator 1 open, RLY2 – actuator 1 close,
RLY3 – actuator 2 open, RLY4 – actuator 2 close.
High temp
Low temp
Probe damage
Probe deviation
Disabled/95.0°F
Disabled/60.0°F
Disabled
Disabled/5°F
Variable stage settings (VAR1 and 2)
Other setting defaults
Range (on full at)
Set point
Off at
Idle speed/min heat
86.0°F
80.0°F
75.0°F
20%
Group set point/growth curve defaults
Current day
Step 1, 4 days
Step 2, 10 days
Step 3, 10 days
Step 4, 10 days
Step 5, 10 days
Step 6, 10 days
Step 7, 20 days
Group set point
0/off
85.0°F
80.0°F
75.0°F
70.0°F
65.0°F
60.0°F
60.0°F
75.0°F
Actuator settings
Curtain settings
Duty cycle settings
Heat/cool settings
None assigned
None assigned
None assigned
None assigned