EasyManuals Logo

Planet IMG-2100T User Manual

Planet IMG-2100T
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
User’s Manual of IMG-2x00T Modbus Gateway Series
54
4.5.2.5 ASCII Master mode
This function allows the users to use Modbus ASCII master device and Modbus TCP device to achieve communication. The
operation mode of the Industrial Modbus Gateway is set to ASCII Master. The TCP client mode topology in Figure 4-5-11
appears.
Figure 4-5-11: ASCII Master Mode Topology
The TCP client mode screenshot in Figure 4-5-12 appears.
Figure 4-5-12: ASCII Master Mode Screenshot
4.5.3 MB COM
This page is to create virtual COM port for Modbus gateway. The default is disable.
4.5.4 Modbus Config
4.5.4.1 Router
The Modbus Gateway support four Modbus masters in each serial port which can communicate with the Modbus slave devices.
It can be connected to a serial port by IP address or TCP port. The screen in Figure 4-5-14 appears.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Planet IMG-2100T and is the answer not in the manual?

Planet IMG-2100T Specifications

General IconGeneral
BrandPlanet
ModelIMG-2100T
CategoryGateway
LanguageEnglish

Related product manuals