Page #69 background imageLoading...
Page #69 background image
Module/
slot
Index Name Module
name
Identifi‐
cation
(hex)
Type Data
flow *
Description
2 Contact
memory
u8 - see "Batch Memory"
8 1 Con‐
centra‐
tion rate
Con‐
centra‐
tion
C0,83,8
3
f32 S Concentration setting setpoint (only
in
‘Concentration’
operating mode)
2 Actual
concen‐
tration
f32 R Actual value of concentration setting
(only in
‘Concentration’
operating
mode)
* R = read, W = write
Tab. 42: Error / Warning
Module
/slot
Index Name Module
name
Identifi‐
cation
(hex)
Type Data
flow *
Description
9 1 Error Error /
Warning
40.85 u32 R Bit Name Function
0 Minimum Metering
medium level is
too low
1 Batch Too many
metering
strokes: >
100,000
2 Analog <
4mA
Analogue cur‐
rent is less than
4 mA
3 Analog >
23mA
Analogue cur‐
rent is greater
than 23 mA
4 Tem‐
perature
fault
Temperature
too high
5 Hose
rupture
Metering hose
damaged
6 -
7 -
8 -
9 -
10 -
11 -
12 -
13 Bus
error
Bus error
reported by the
module
14 System
error
System compo‐
nents faulty -
see display
Supplementary Operating Instructions for PROFINET
®
69

Table of Contents

Other manuals for ProMinent DULCO flex Control

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProMinent DULCO flex Control and is the answer not in the manual?

ProMinent DULCO flex Control Specifications

General IconGeneral
BrandProMinent
ModelDULCO flex Control
CategoryWater Pump
LanguageEnglish

Related product manuals