Tab. 43: Strokes / quantity and individual data
Module/
slot
Index Name Module
name
Diag.
number
Identifi‐
cation
(hex)
Type Data
flow *
Description
10 1 Reset
stroke
counter
Strokes
/quan‐
tity
20 C0,81,
C5
u8 S If the value changes from 1
to 0, the
‘Stroke counter’
(total number of strokes) is
reset
2 Reset
quantity
counter
21 u8 If the value changes from 1
to 0, the
‘Quantity counter’
(total number of litres) is
reset
3 Stroke
counter
22 u32 R Counts the number of
strokes - since the last
reset (
‘Stroke counter’
)
4 Quan‐
tity
counter
23 f32 Counts the metering
volume in litres - since the
last reset (
‘Quantity
counter’
)
5 Litres
per
stroke
24 f32 Litres per stroke
6 Live‐
span
hose
25 u32 Hose service life
* R = read, W = write
In conformity with PROFIBUS
®
standard, the device makes the
[Get_Sl_Diag]
service available. The diagnostics data comprise
standard diagnostics information (6 bytes according to PRO‐
FIBUS
®
standard) and any possible diagnostics data specific to the
device. A maximum of 63 bytes can be added for the device-spe‐
cific diagnostics data. Of these, the first 4 bytes in the PROFIBUS
®
standard are specified:
Encode the sign_len byte as follows:
Length of the status DU including the header byte: 04..63
‘Device-related diagnostics’ specification: 00 constant
Encode the status_type byte as follows:
Status type: 48 (manufacturer-specific)
‘Status’ specification: 1 constant
Encode the slot_number byte as follows:
Slot number: 0 (because only slot 0 is being used)
Diagnostic telegrams
Supplementary Operating Instructions for PROFINET
®