Setting Possible values
Starting
value
Increment Lower value Upper
value
Remark
[↳PUMPMA
X]
180 RPM 1 1 RPM 500 RPM Maximum
stroke rate of
the low power
relay (fre‐
quency relay)
[mA OUT]
(Issued vari‐
able of the
mA
standard
signal
output)
meas val off off
meas val meas val =
measured vari‐
able (conduc‐
tivity)
corr val corr val = cor‐
rection variable
dosing dosing = con‐
trol value
manual manual =
Manual
[↳RANGE]
4 - 20 mA 0 - 20 mA Range of the
mA standard
signal output
4 - 20 mA
[↳0/4 mA]
0.01 mS/cm 0.001 0.000 uS/
cm
2.000 S/cm
[↳20 mA]
0.02 S/cm 0.001 0.000 uS/
cm
2.000 S/cm
[↳0/4 mA]
0.0 °C 0.1 °C 0.0 °C 150.0 °C Temp value
assigned 0/4
mA
[↳20 mA]
100.0 °C 0.1 °C 0.0 °C 150.0 °C Temp. value
assigned 20
mA
[↳0/4 mA]
32.0 °F 0.1 °F 32.0 °F 302.0 °F Temp. value
assigned 0/4
mA
Operating menus
75