Outputs galvanically isolated from other switching parts by reinforced insulation.
Digital input
Open circuit voltage 22 V DC max.
Short circuit current 6.5 mA
Max.switching frequency Static. For switching processes like
‘PAUSE’
,
‘HOLD’
, etc.
NOTICE!
Do not supply with voltage
To connect an external semiconductor or mechanical switch.
mA output 0 ... 20 mA 4 ... 20 mA manual
current range 0 ... 20.5 mA 3.8 ... 20.5 mA 0 ... 25 mA
In the event of
a fault
0 or 23 mA 3.6 or 23 mA
Max. load
480 W at 20.5 mA
Max. output
voltage
19 V DC
Overvoltage-
resistant up to:
± 30 V
Output accu‐
racy
0.2 mA
The mA output is galvanically isolated from all other connections (500 V)