Reference MVI56E-MNETC/MNETCXT ♦ ControlLogix Platform
User Manual Modbus TCP/IP Client Enhanced Communication Module - Client/Server
Page 156 of 172 ProSoft Technology, Inc.
September 20, 2018
5.5.5 Writing the Ethernet Settings to the Module
Expand the MVI56EMNETCETHERNET controller tag.
Set the new Ethernet configuration in MVI56EMNETCETHERNET.Config:
Move a value of 1 to MVI56EMNETCETHERNET.Write.
After the message is executed, the MVI56EMNETCETHERNET.Write bit resets
to 0.