EasyManua.ls Logo

ProSoft MVI56E-MCMR - Port Configuration

ProSoft MVI56E-MCMR
223 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuring the MVI56E-MCMR Module MVI56E-MCMR ControlLogix Platform
User Manual Modbus Communication Module with Reduced Data Block
Page 54 of 223 ProSoft Technology, Inc.
The sample configuration values configure the module database to store
WRITEDATA[0 to 599] in registers 0 to 599, and READDATA[0 TO 599] in registers
1000 to 1599, as shown in the following illustration.
Important: If you need to configure different values for the Read Register Count and Write
Register Count parameters, you must also configure the same values in the user-defined data type
MCMRData in the sample program (page 37).
2.3.3 Port Configuration
The MODBUS PORT X configuration parameters are used when the module is
configured as a Modbus Master device. Port 1 and Port 2 each have their own
set of configuration parameters.
Note: Any changes made within the configuration file must be downloaded to the MVI56E-MCMR
module from ProSoft Configuration Builder.
In ProSoft Configuration Builder, expand the MVI56E-MCMR node, and then
expand the MCM PORT 1 node. Double-click the MODBUS PORT 1 icon. In the
EDIT - MODBUS PORT 1 dialog box, click to highlight the Type parameter, and then
select MASTER from the dropdown list.

Table of Contents

Related product manuals