Configuring the MVI56E-MCMR Module MVI56E-MCMR ControlLogix Platform
User Manual Modbus Communication Module with Reduced Data Block
Page 84 of 223 ProSoft Technology, Inc.
Value
Description
Float offset
Internal address for floats
Internal Slave ID
Valid values are 1 to 247
Minimum Response Delay
0 to 65535 milliseconds to delay before response
Bit Input Offset
Defines the starting address within the module for 1x Modbus
addressing. A value of 0 sets 10001 to 10016 as address 0 in the
MVI56E-MCMR module.
Word Input Offset
Defines the starting address within the module memory for 3x
registers.
Output Offset
Defines the starting address within the module for 0x coils.
Holding Register Offset
Defines the starting address within the module for 4x addressing.
Use Guard Band Timer
YES or NO
Packet gap timeout for messages
Guard Band Timeout
0 to 65535
A value of 0 uses the default baud rate, or you can set a timeout value
in milliseconds.
2.4.4 Floating-Point Data Handling (Modbus Slave)
In most applications, the use of floating-point data requires no special handling.
1 Copy the data to and from the MVI56E-MCMR module with a tag configured
as a data type REAL in the ControlLogix processor.
Each floating-point value will occupy 2 registers on the Modbus network.
Some Master devices use Enron or Daniel Float data. These types of floats
require one Modbus register for each float in the module memory. If your
Master requires this addressing, refer to the following section.
For standard floating-point data handling, the following is an example of
copying 10 floats to the module.
2 First, configure a tag within the ControlLogix processor.
3 Then configure a COP statement within the main routine to copy this tag to
the module’s MCMR.DATA.WRITEDATA array.
The length of the copy statement is determined by the Dest file size. To copy 10
floats from the MCM_Write_Floats array to the MCMR.DATA.WRITEDATA array,
the length of the COP statement must be set to a value of 20.
To copy data from the MVI56E-MCMR module to a floating-point tag within the
ControlLogix processor

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProSoft MVI56E-MCMR and is the answer not in the manual?

ProSoft MVI56E-MCMR Specifications

General IconGeneral
BrandProSoft
ModelMVI56E-MCMR
CategoryControl Unit
LanguageEnglish

Related product manuals