EasyManuals Logo

ProSoft MVI56E-MCMR User Manual

ProSoft MVI56E-MCMR
223 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #74 background imageLoading...
Page #74 background image
Configuring the MVI56E-MCMR Module MVI56E-MCMR ControlLogix Platform
User Manual Modbus Communication Module with Reduced Data Block
Page 74 of 223 ProSoft Technology, Inc.
Write Floats to Slave Device
To issue a Write command to Floating-Point addresses, use the configuration in
the following table. The table describes the Modbus Map for the slave device.
Value
Description
Type
40261
KW
Demand (power)
Float. upper 16 bits
40263
VAR
Reactive Power
Float. upper 16 bits
40265
VA
Apparent Power
Float. upper 16 bits
40267
Power Factor
Float. upper 16 bits
40269
VOLTS
Voltage, line to line
Float. upper 16 bits
40271
VOLTS
Voltage, line to neutral
Float. upper 16 bits
40273
AMPS
Current
Float. upper 16 bits
You must use a COP statement to copy the data from floating-point data tags
within the ControlLogix processor, into the MCMR.DATA.WRITEDATA array used
by the MVI56E-MCMR module. Below is an example.
The length of this COP statement must now be 14. This will COP as many of the
MCM_FLOAT_DATA values required to occupy the MCMR.DATA.WRITEDATA
array for a length of 14. This will take 7 registers, MCM_FLOAT_DATA[0] TO [6],
and place that data into MCMR.DATA.WRITEDATA[0] TO [13].
You must configure the command to write all 7 floats (14 Modbus addresses) as
follows.
The above command will take the data from MCMR.DATA.WRITEDATA[0] TO [13]
and write this information to Modbus Slave Device Address 1 at data addresses
40261 to 40274.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProSoft MVI56E-MCMR and is the answer not in the manual?

ProSoft MVI56E-MCMR Specifications

General IconGeneral
BrandProSoft
ModelMVI56E-MCMR
CategoryControl Unit
LanguageEnglish

Related product manuals