EasyManua.ls Logo

Protege PRT-CTRL-SE - Page 13

Protege PRT-CTRL-SE
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Figure 10 - EOL Jumper
Always connect the Protégé® SE Integrated System Controllers NA and NB terminals to the NA and
NB terminals of the expansion devices and keypads. The N+ and N- must go to a 12V power supply
source as shown in gure 9 below.
Figure 9 - Network Power Connecon
?
The diagram above shows a power connecon taken from the Auxiliary Power
Outputs on the Protégé® SE Integrated System Controllers zone terminals. It is
recommended to only use this connecon for smaller systems where limited power
is required. For larger installaons use a separate power supply.
EOL OFFEOL ON
?
The EOL (End Of Line) jumper seng must be set in the on posion for the rst and
last expansion device only.
!
The 12V N+ and N- Communicaon Input must be supplied from only one point.
Connecons from more than one 12V supply may cause failure or damage to the
units supplying power.