8.2 Defaulng a Controller
The Protégé® SE Integrated System Controller can be set back to factory default using the following
procedures. This will reset all internal data and event informaon.
Step 1
Remove power from the controller by disconnecng the AC and baery supply.
Step 2
Turn ON Conguraon Dip Switch 4.
Step 3
Power up the Protégé® SE Integrated System Controller by turning on the AC supply.
Step 4
Turn OFF Conguraon Dip Switch 4 once the Protégé® SE Integrated System Controller is
indicang normal status by ashing the green status indicator. The system will now be defaulted
with all programming and sengs returned to factory conguraon.
?
Defaulng the Protégé® SE Integrated System Controller will not reset the IP
address. To reset an IP address refer to the secon Conguraon Switch on
page 24.