EasyManua.ls Logo

Protege PRT-CTRL-SE - 6.0 Inputs; 6.1 Zones

Protege PRT-CTRL-SE
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
!
The zones 9-12 and 13-16 can operate as either general purpose zone inputs or as
onboard reader inputs. If used as general purpose zone inputs then make sure that
these input are not dened in the onboard reader set up. Please refer to the table
on page 16 for the default sengs of these zones.
6.0 Inputs
6.1 Zones
The Protégé® SE Integrated System Controller has 16 Zone Inputs. The Protégé® SE Integrated
System Controller also monitors 64 trouble zones used to report trouble condions. A trouble zone
represents a trouble condion within the system. The trouble zone will open or go in to alarm
when that trouble condion is present, and close or return to normal when the trouble condion
restores. As an example trouble zone CP001:01 will open or go in to alarm when the tamper input
on the Protégé® SE Integrated System Controller is open.
The Protégé® SE Integrated System Controller can monitor and control thousands of zone and
trouble zone inputs by using the expansion modules.
The Protégé® SE Integrated System Controller can monitor the state of up to 16 zone inputs such as
magnec contacts, moon detectors and temperature sensors. Devices connected to these zones
can be installed to a maximum distance of 300m (1000) from the Protégé® SE Integrated System
Controller when using 22 AWG. The Protégé® SE Integrated System Controller supports normally
opened and normally closed conguraons with or without EOL resistors.
Zones can be programmed from the Protégé® Alphanumeric LCD Keypad (PRT-KLCD) or using the
Protégé® System Management Suite applicaon (PRT-SMGT). CP001:01 to CP001:16 represent
Zone 1 to Zone 16 on the Protégé® SE Integrated System Controller.
When using a zone with the EOL resistor conguraon, the Protégé® SE Integrated System
Controller generates an alarm condion when the state of a zone is toggled and generates a
tamper alarm condion when a wire fault (short circuit) or a cut (tampered) in the line occurs.
Zones default to require the EOL resistor conguraon.
Figure 21 - EOL Resistor Zone Conguraon
+AUX- Z1 COM COMZ2 Z3 Z4
N.C Zone Contact
N.C T a mper 1K 1K