It is important that the unit when installed is located in a dry cool locaon that
is not aected by humidity. Do not locate the unit in an air condioning or boiler
room that can exceed the temperature or humidity specicaons.
33
13.2 Current and Validaon Example 2
The example shown below refers to the specicaon’s table needed to help ensure the correct
installaon of the Protégé® SE Integrated System Controller. Specicaons have to be validated to
ensure that individual maximum currents and total combined current are not exceeded.
External Devices Connected to Panel
8x EDGE PIR Moon Detectors (Z1 to Z8)
2x 15W Siren (500mA @ 13.8VDC)
Current Consumpon
Total Combined Current Available 1.8A (1800mA)
Operang Current 280mA (Typical)
Baery Charging 350mA (Standard Current Charging)
DC Output (Auxiliary) 8x EDGE PIR Moon Detectors @ 15mA each (Total 120mA)
Siren on Bell 1 Output 500mA
Siren on Bell 2 Output 500mA
Total Consumpon 1.75A (1750mA)
Validaon
Is the total DC Output (Auxiliary) current less or equal to 700mA? Yes, it is 120mA
P
Is Bell 1 current less or equal to 700mA? Yes, it is 500mA
P
Is Bell 2 current less or equal to 700mA? Yes, it is 500mA
P
Is the total consumpon less or equal to 1.8A (1800mA)? Yes, it is 1.75A (1750mA)
P