Cabinet Requirements
You can mount the Pulse Secure Gateway (except for the MAG2600) in a cabinet that contains a 19-in rack.
There are requirements for:
•
Cabinet size
•
Cabinet clearance
•
Cabinet airflow
Table: Cabinet Requirements and Specifications
•You can mount the Pulse Secure Gateway in a cabinet that contains a 19-
in. rack as defined in Cabinets, Racks, Panels, and Associated Equipment
(document number EIA-310–D) published by the Electronics Industry
Association (http://www.eia.org).
•The rack must meet the strength requirements to support the weight of the
Pulse Secure Gateway.
•The minimum cabinet size must be accommodate the maximum external
dimensions of the Pulse Secure Gateway.
•The outer edges of the mounting brackets extend the width of the chassis
to 19-in. (48.3-cm).
•The minimum total clearance inside the cabinet is 30-in. (76.2-cm) between
the inside of the front door and the inside of the rear door.