AXIS-H EMC
Actuators are constantly moving,
actuators buzzing
RAUCH Landmaschinenfabrik GmbH D-76547 Sinzheim
Customer service hotline: +49 (0)7221 985 250
E-mail: service@rauch.de
Page
1
of
1
29.10.2014
Chapter 780
Check the voltage supply
Check the battery contacts, fuses and
cables for corrosion and damage
Check the actuators for sluggishness and
function
+ Disengage the piston rod; it must be
possible to rotate the piston rod manually
+ Check the housing and cable inlet for
damage
Check the machine cable + Check the connectors for humidity and
corrosion
+ Check the PG connection (update
connection) for humidity and corrosion
+ Check the connections at the implement
Check the implement ECU
+ Check the contact points
+ Check the software version
+ Check the implement ECU for damage
and ingress of humidity
Check the parameters
+ Check the parameters P, I, D for
actuator control in the control parameters
menu and reset them to default (perform
software update)
=> see chapter 4