3 V lithium battery
Service life: At least five years.
Fans
Fans are mechanical wear components. Their service life is extremely tempera-
ture-dependent.
Service life of the fan:
● 95,000 hours at 24°C
The fan operating hours counter can be requested via the control.
6 Ambient conditions
In operation Transport Storage
Max. ambient tempera-
ture
+5°C to +55°C -25°C to +70°C -25°C to +70°C
Relative humidity RH -2; 5 % to 95 % acc.
DIN EN 61131-2,
Condensing not permit-
ted.
RH -2; 5 % to 95 % acc.
DIN EN 61131-2,
Condensing not permit-
ted.
RH -2; 5 % to 95 % acc.
DIN EN 61131-2,
Condensing not permit-
ted.
Air pressure Up to 2700 m above sea
level acc. to DIN 60204.
Above 2700 m above
sea level, see chapter
10.7.8 "Information on
the control use above
2,700 m above sea lev-
el" on page 37.
Up to 3,000 m above
sea level acc. to
DIN 60204.
Above 2700 m above
sea level, see chapter
10.7.8 "Information on
the control use above
2,700 m above sea lev-
el" on page 37.
Up to 3,000 m above
sea level acc. to
DIN 60204.
Above 2700 m above
sea level, see chapter
10.7.8 "Information on
the control use above
2,700 m above sea lev-
el" on page 37.
Mechanical strength Max. vibration:
Frequency range: 10 Hz
to 150 Hz
Excursion: 0.075 mm
at 10 Hz to 57 Hz
Acceleration: 1 g
at 57 Hz to 150 Hz
Acc. to EN 60068-2-6
Max. shock:
15 g acc. to
EN 60 068-2-27, no dis-
turbance of the function.
Max. shock:
15 g acc. to
EN 60 068-2-27, no dis-
turbance of the function.
Tab. 6-1: Ambient conditions
Bosch Rexroth AG
Ambient conditions
L25, L45, L65, L75 and L85
8/53
DOK-CONTRL-IC*LX5*****-IT02-EN-P